Issue Date: November 22, 1995
Revision Date: March 24, 2011
FE Petro, Inc.
STP-MLD Pipeline Leak Detector
Automatic Mechanical Line Leak Detector
Certification | Leak rate of 3.0 gph with PD = 100% and PFA = 0%. |
---|---|
Leak Threshold | 2.0 gph. A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold. |
Applicability | Gasoline, diesel, aviation fuel, fuel oil #4. Other liquids may be tested after consultation with the manufacturer. |
Specification | System tests fiberglass and steel pipelines. Tests are conducted at operating pressure. |
Pipeline Capacity | Maximum of 129.14 gallons. |
Waiting Time | None between delivery and testing. None between dispensing and testing |
Test Period | Response time is less than 30 seconds. |
System Features | Permanent installation on pipeline. Automatic testing of pipeline. Preset threshold. Single test to determine if pipeline is leaking. Restricted flow to dispenser if leak is declared. |
Calibration | Equipment must be checked annually for capability of detecting a line leak of 3.0 gph and, if necessary, calibrated in accordance with manufacturer's instructions. |
- Franklin Fueling Systems
3760 Marsh Road
Madison, WI 53718
Tel: (800) 225-9787
Email: info@franklinfueling.com
URL: www.franklinfueling.com - Evaluator: Ken Wilcox Associates Tel: (816) 443-2494 Date of Evaluation: 07/01/92
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.