Issue Date: June 8, 2009
Preferred Utilities Manufacturing Corporation
PWCN4-CDXRxxx Controller, RBS Non-Discriminating Sensors for Sumps and Containments; PS-LDS Non-Discriminating Sensor for Sumps and Containments; PLS Non-Discriminating Sensor for Reservoirs
Interstitial Detector (Liquid-Phase)
Detector
Output Type | Qualitative |
---|---|
Sampling Frequency | Continuous |
Operating Principle | Reed switch/float |
Test Results
Diesel | Water | |
---|---|---|
Detection time (sec) | <1 | <1 |
Fall time (sec) | <1 | <1 |
Lower detection limit (in) | 0.411 | 0.120 |
Diesel | Water | |
---|---|---|
Detection time (sec) | <1 | <1 |
Fall time (sec) | <1 | <1 |
Lower detection limit (in) | 0.267 | 0.255 |
Diesel | Water | |
---|---|---|
Detection time (sec) | <1 | <1 |
Fall time (sec) | <1 | <1 |
Lower detection limit (in) | 2.443 | 2.220 |
Comments
Control panel models: PWCN4-CDXRxxx for liquid level sensors;
Can be used in normally open or closed positions, and wired to alarm or to shut down equipment.
Minimum Specific Gravity: RBS=0.65, PS-LDS=0.75; PLS=0.5
- Preferred Utilities Manufacturing Corporation
31-35 South Street
Danbury, CT 06810
Tel: (203) 743-6741 - Evaluator: Ken Wilcox Associates
Tel: (816) 443-2494
Date of Evaluation: 1/20/09
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.