Issue Date: May 27, 2004
Revision Date: June 10, 2004
SGB
(Sicherungsgeratebau GmbH)
Overpressure
Leak Detection System Model DLR-G
CONTINUOUS
INTERSTITIAL LINE MONITORING METHOD (PRESSURE/VACUUM)
Certification:
Certified per European leak detection standard
EN 13160-2, Part 2, as a Class I leak detection system.
Operating
Principle:
System uses pressurized nitrogen gas to continuously
maintain an overpressure within the interstitial space of
double-walled piping. System is designed to activate a visual
and acoustic alarm before stored product can escape to the
environment. System is capable of detecting breaches in both
the inner and outer walls of double-walled piping.
Alarm
Condition:
System alarms when a leak occurs which causes the
pressure within the interstitial space to decrease to the
“Minimum Interstitial Space Alarm Pressure” (see table below).
Applicability:
Double-walled piping, underground or aboveground,
having a design strength capable of safely sustaining the
required operating pressure in the interstitial space. Piping
may convey flammable, combustible, or non-combustible liquids
including gasoline, gasohol, diesel, heating oil #2, kerosene,
aviation fuel, motor oil, and acidic or caustic solutions.
Note: Conveyed product must not react with pressurized nitrogen.
Interstitial space to be monitored must not exceed 150 ft3.
Manufacturer's
Specifications:
The leak detector can be configured to monitor
primary lines with operating pressures up to 120 psi, as indicated
in the following table. The interstitial space shall be rated
for the operating pressure (interstitial space refilling “off”
pressure) of the leak detector, as indicated in the following
table. Pressures shall be set as follows:
The DLR-G leak detector is not
explosion protected. Do not install in a volatile, combustible
or explosive atmosphere. Install the detector inside the building
in a dry, frost-proof area. When using nitrogen gas, ensure
that the room is ventilated according to applicable codes
due to asphyxiation hazard. If installed outside in a protected
area, place in a weatherproof protection box with a transparent
lid.
Calibration:
Functional and operational safety tests must be
performed annually in accordance with manufacturer's instructions.
Comments:
Interstitial space is tested continuously.
System can operate in two modes: with or without a nitrogen
bottle continuously connected. Nitrogen bottle must be connected
unless the piping is “impermeable” (e.g., double-walled steel).
Pressure is generated by inert gas bottle (nitrogen) and is
measured and controlled by a pressure switch.
This system may not be compatible with all secondarily contained
tanks and/or piping. Always consult with the tank and/or piping
manufacturer and the manufacturer's applicable recommended
installation practices before installing this system, or damage
may be caused to the tank or piping by its use.