Issue Date: November 22, 1995
Revision Date: April 18, 1997
SIR Monitor
(originally listed as Environmental Management Technologies)
SIR Monitor
Statistical Inventory Reconciliation Test Method (Quantitative)
Detector
Certification | Leak rate of 0.1 gph with PD = 99% and PFA = 1%. "If a method meets the requirement for detecting a leak rate of 0.1 gph, it will meet the requirement for 0.2 gph.", according to "Standard Test Procedures for Evaluating Leak Detection Methods: Statistical Inventory Reconciliation Methods", EPA/530/UST-90/007, June 1990, Section 7.2.3, page 30. |
---|---|
Leak Threshold | If the absolute value of the calculated leak rate (gain or loss) is less than the leak threshold and the minimum detectable leak rate is less than or equal to 0.1 gph, the test result is "pass." If the absolute value of the calculated leak rate is greater than or equal to the leak threshold, the result is "fail." If the minimum detectable leak rate exceeds 0.1 gph and the absolute value of the calculated leak rate is less than the leak threshold, the test result is "inconclusive." |
Applicability | Gasoline, diesel. Other more viscous liquids may be tested after consultation with the vendor. |
Tank Capacity | Maximum of 18,000 gallons. |
Data Requirement | Minimum of 90 days of product level and flow through data are required before making the first evaluation. Following the first evaluation, subsequent evaluations are made based on minimum of 30 days of data. |
Comments | Not evaluated using data from manifolded tank systems. Of 41 data sets submitted for evaluation, 5 were inconclusive. Median monthly throughput of tanks evaluated was 14,600 gallons. Leak rates of 0.05, 0.1, and 0.2 gph were used in evaluation. Data sets evaluated were supplied by vendor. |
- SIR Monitor
P.O. Box 2791
Murfreesboro, TN 37133
Tel: (615) 895-2872 - Evaluator: Nathan Adams,
Middle Tennessee State University
Tel: (615) 898-2644
Date of Evaluation: 11/05/92
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.