Issue
Date: November 22, 1995
Revision Date: February 22, 2017
Syscorp,
Inc.
Store
Vision Version E.2
STATISTICAL
INVENTORY RECONCILIATION TEST METHOD (QUALITATIVE)
Certification
|
Leak
rate of 0.2 gph with PD = 95.7% and PFA = 0%.
|
Leak
Threshold
|
If
the absolute value of the calculated leak rate (gain or
loss) is less than the leak threshold and the minimum
detectable leak rate is less than or equal to 0.2 gph
, the test result is "pass." If the absolute
value of the calculated leak rate is greater than or equal
to the leak threshold, the result is "fail."
If the minimum detectable leak rate exceeds 0.2 gph and
the absolute value of the calculated leak rate is less
than the leak threshold, the test result is "inconclusive."
|
Applicability
|
Gasoline,
diesel.
Other more viscous liquids may be tested after consultation
with the vendor.
|
Tank
Capacity
|
Maximum
of 12,000 gallons.
|
Data
Requirement
|
Minimum
of 29 days of product level and flow through data.
|
Comments
|
Not
evaluated using manifolded tank systems.
Of 120 data sets submitted for evaluation, 32 were inconclusive.
Median monthly throughput of tanks evaluated was 8,097
gallons.
Leak rate of 0.2 gph was used in evaluation. Data sets
evaluated were supplied by evaluator.
This method does not meet the Federal UST requirement for Statistical Inventory Reconciliation to report a quantitative result with a calculated leak rate. (40 Code of Federal Regulations, part 280.43(h)(1).)
|
Syscorp,
Inc.
|
Evaluator: Midwest Research Institute
|
531
HighlandPark Circle
|
Tel: (816) 753-7600
|
Birmingham,
AL 35242
|
Date
of Evaluation: 09/30/93
|
Tel: (205) 853-0004
|
|
|