Issue Date: November 22, 1995
Revision Date: January 12, 2015
Triangle Environmental, Inc.
TEI System 5000, Version 1.0, Version 1.0W
Non-Volumetric Tank Tightness Test Method (Vacuum)
Certification | Leak rate of 0.1 gph with PD = 100% and PFA = 0%. |
---|---|
Leak Threshold | A tank system should not be declared tight when the acoustic noise level of the tank under vacuum is greater than the calibrated background acoustic noise level (prior to evacuation). A tank system should not be declared tight if any water ingress is detected. |
Applicability | Gasoline, diesel, aviation fuel, fuel oil #4, waste oil. |
Tank Capacity | Maximum of 20,000 gallons. Tank must be minimum 14% full. Microphone should be located within 24 feet of all points within the tank. |
Waiting Time | None between delivery and testing. |
Test Period |
|
Test Pressure | Vacuum as directed in operating instructions. If vacuum cannot be maintained, see manufacturer's instructions. |
Temperature | Acoustic signal is independent of product temperature. |
Water Sensors |
|
Groundwater | Depth to groundwater in tank excavation backfill must be determined. Version 1.0 can only be used when groundwater is below bottom of tank. Version 1.0W must be used when groundwater is above bottom of tank. |
Calibration | Acoustic sensor must be calibrated before each test in accordance with manufacturer's instructions. When using Version 1.0W, Triangle TEI System 5000 Water Sensor or Estabrook EZ-3 Conductivity Water Sensor must be calibrated before each test in accordance with manufacturer's instructions. |
Comments | Manifolded tank systems must be isolated prior to test. Evaluated using unleaded gasoline. Microphone was 24 feet away from the leak source during evaluation. Headphones are used during test to listen for air ingress signal. Noise signals are tape recorded rather that recording the noise levels in decibels. Vacuum test method may not be effective in some tank excavation backfill (such as clay) because it may plug holes in tank. If soil is saturated with product, air or water ingress may not be detected by vacuum test. A well point in tank excavation backfill may help identify presence of this condition. |
- Triangle Environmental, Inc.
3726 Park Place
Montrose, CA 91020
(818) 301-7777 - Evaluator: United States Testing Company
Tel: (213) 723-7181
Date of Evaluation: 02/04/93 - Evaluator: Consolidated Testing Laboratories, Inc.
(550) 592-3555
Date of Evaluation: 01/20/98
Home | Vendors: A–F | Vendors: G–M | Vendors: N–S | Vendors: T–Z | Method Index
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.