Issue Date: August 27, 2007

Tyco Thermal Controls LLC

TraceTek Alarm and Locator Modules with TT-FFS Fast Fuel Sensor

Interstitial Detector (Liquid-Phase) and Liquid-Phase Out-Of-Tank Product Detector

Detector

Output Type Qualitative
Sampling Frequency Continuous
Operating Principle Electrical conductivity

Test Results

TT-FFS (.005" fuel on water)

  Synthetic Gasoline Diesel Jet-A Fuel Crude Oil
Response time (min:sec) <1 <1 <1 2:33

TT-FFS (.024" fuel on flat surface)

  Synthetic Gasoline Diesel Jet-A Fuel Crude Oil
Response time (min) <1 <1 <1 11

Specificity Results

Activated: synthetic gasoline, diesel, jet-A fuel, crude oil.
Probability of Detection: 100% for all tested liquids with 92% to 100% confidence interval.
Not Activated: water

Comments

All data points are the average of 6 samples.
Dry surface fuel layer depth estimated at .005" for gasoline, diesel and jet-A, .024" for crude oil.
Fuel layer for fuel floating on water estimated to be .005" for all tests.
Sensors can be cleaned and reset by soaking in naphtha and allowing them to dry in the air for 1 hour
Sensors that do not reset must be replaced.
Sensor can be periodically tested with naphtha. Manufacturer recommends 6 month interval.

  • Tyco Thermal Controls LLC
    300 Constitution Dr.
    Menlo Park, CA 94025-1164
    Tel: (800) 545-6258
  • Evaluator: Carnegie Mellon Research Institute
    Tel:(412) 268-3495
    Date of Evaluation: 09/06

Home |  Vendors: A–F |  Vendors: G–M |  Vendors: N–S |  Vendors: T–Z |  Method Index

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment. Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to our expanded DISCLAIMER page.